Fresh Air Processing Indoor Unit \\

TMV 5

Fresh Air Processing Indoor Unit

With unique system design, the unit is able to process the outdoor air and then supply the processed air to the room. The factory setting temperature of the processed  outdoor air in the cooling mode is close to the indoor setting temperature (22 ) so that you can enjoy much fresher air and more comfort and also the required load the indoor unit can be reduced.

Why MULTI VRF? Download PDF

GENERAL CHARACTERISTICS

Compact Design Compact Design
Fresh air Fresh air
High ESP High ESP
Maximum capacity 45kW Maximum capacity 45kW
energy-saving energy-saving
High BSM High BSM

TECHNICAL SPECIFICATION

Model
Capacity - Cooling
kW
Capacity - Heating
kW
Power supply
V/f/Hz
Cooling power input
kW
Heating power input
kW
Noise (sound pressure level)
dB(A)
Air volume
m3/h
ESP
Pa
Gas pipe size
mm
Liquid pipe size
mm
Drainpipe - External Dia
mm
Dimension (WxDxH)
mm
Net weight
kg
Max. Fuse Current
A
TMV-NX140P/A(X1.2)-K
Capacity - Cooling (kW): 14.00
Capacity - Heating (kW): 10.00
Power supply (V/f/Hz): 220-240/1/50
Cooling power input (kW): 0.36
Heating power input (kW): 0.36
Noise (sound pressure level) (dB(A)): 42
Air volume (m3/h): 1200
ESP (Pa): 150/200
Gas pipe size (mm): 15.90
Liquid pipe size (mm): 9.52
Drainpipe - External Dia (mm): 30
Dimension (WxDxH) (mm): 1463x756x300
Net weight (kg): 63.50
Max. Fuse Current (A): 3.70
TMV-NX224P/A(X2.0)-M
Capacity - Cooling (kW): 22.40
Capacity - Heating (kW): 16.00
Power supply (V/f/Hz): 380-415/3/50
Cooling power input (kW): 0.74
Heating power input (kW): 0.74
Noise (sound pressure level) (dB(A)): 47
Air volume (m3/h): 2000
ESP (Pa): 200/300
Gas pipe size (mm): 19.05
Liquid pipe size (mm): 9.52
Drainpipe - External Dia (mm): 30
Dimension (WxDxH) (mm): 1500x1000x500
Net weight (kg): 130
Max. Fuse Current (A): 4.70
TMV-NX280P/A(X2.5)-M
Capacity - Cooling (kW): 28.00
Capacity - Heating (kW): 20.00
Power supply (V/f/Hz): 380-415/3/50
Cooling power input (kW): 0.76
Heating power input (kW): 0.76
Noise (sound pressure level) (dB(A)): 48
Air volume (m3/h): 2500
ESP (Pa): 200/300
Gas pipe size (mm): 22.20
Liquid pipe size (mm): 9.52
Drainpipe - External Dia (mm): 30
Dimension (WxDxH) (mm): 1500x1000x500
Net weight (kg): 134
Max. Fuse Current (A): 5.40
TMV-NX280P/A(X3.0)-M
Capacity - Cooling (kW): 28.00
Capacity - Heating (kW): 20.00
Power supply (V/f/Hz): 380-415/3/50
Cooling power input (kW): 1.06
Heating power input (kW): 1.06
Noise (sound pressure level) (dB(A)): 51
Air volume (m3/h): 3000
ESP (Pa): 200/300
Gas pipe size (mm): 22.20
Liquid pipe size (mm): 9.52
Drainpipe - External Dia (mm): 30
Dimension (WxDxH) (mm): 1500x1000x500
Net weight (kg): 134
Max. Fuse Current (A): 5.50
TMV-NX450P/A(X4.0)-M
Capacity - Cooling (kW): 45.00
Capacity - Heating (kW): 32.00
Power supply (V/f/Hz): 380-415/3/50
Cooling power input (kW): 1.24
Heating power input (kW): 1.24
Noise (sound pressure level) (dB(A)): 58
Air volume (m3/h): 4000
ESP (Pa): 200/300
Gas pipe size (mm): 28.60
Liquid pipe size (mm): 12.70
Drainpipe - External Dia (mm): 33
Dimension (WxDxH) (mm): 1700x1100x650
Net weight (kg): 208
Max. Fuse Current (A): 7.60